062367 • Version 1.0 • 14.02.2011
Functional description
Function switch The function switch allows the user to switch between different
modes.
The modes are described below.
Operation modes
This gives a description of each selectable mode:
Mode Description
Ventilation
operation
The evaporator fan will operate according to the speed selected on the
evaporator fan speed switch
O (OFF)
All functions will immediately stop and only the illuminated green lamp
will indicate that the power is still on.
Warning: The evaporator fan will run according to speed selector,
even with the mode selector in “0” OFF position, if temperature inside
the AC-M5 W MKII cabinet exceeds 50 °C.
This will automatically shut down when temperature inside the AC-M5
W MKII cabinet drops below 35 °C
AUTO
The controller will operate to achieve the selected temperature set on
the temperature dial.
The controller decides whether to activate cooling or heating, in order
to maintain desired temperature.