MAINTENANCE/INSPECTION CHECKLIST
(NOTE: Maintenance/inspection items are monthly unless otherwise specified.)
Humidifier (Steam Generator) is equipped:
Inspect drain valve/trap/drain line Check for leaks (makeup water/hoses)
Check humidifier canister (replace if needed) Check and clean fill strainer
Check operation
Record humidifier amp draw L1 A L2 A L3 A
Reheat
Inspect element (and clean if required)
Check wiring
Record amps A
Refrigeration Piping
Check for lines (leaks/lines secure)
Check capillary lines
Condensate Pan and Pump (if equipped)
Check for leaks
Check for debris
Inspect/check float operation
Check pump operation
Condensers (Water-Cooled)
Check for water/glycol leaks (in the piping area) Water regulating valve function
Entering/leaving water temperatures: Entering T °F Leaving T °F
Compressor (Monthly):
Check for oil leaks Check compressor mounting Inspect wire connection
Compressor (Quarterly) Compressor
Record suction pressure
PSIG
Record discharge pressure
PSIG
Record superheat °F
Record subcooling °F
Check high pressure cut-out PSIG
Check low pressure cut-in PSIG
Check low pressure cut-out PSIG
Record compressor current L1 A L2 A L3 A