Field Piping, Remote Condenser/ Condensing Unit Below Evaporator
NOTES:
1. This is the recommended piping. All piping to be per local and/or state code.
2. Condenser to be no more than 15 feet (4.6 M) below evaporator.
3. Slope horizontal lines downward in the direction of the refrigerant flow, 1/2 (13 mm) for
every 10 (3.1 M) feet of line length.
4. Inverted trap needed on suction lines when compressor is outdoors only.