DKG-507 User Manual V-42 (24.05.2013)
- 8 -
The unit has 3 seven segment displays. They show:
-Measured parameters,
-Service counters,
-Statistical counters,
-Program parameters.
The navigation between different screens in a group is made with the MENU► button.
Holding the MENU► button pressed for 1 second makes the display to switch to the next group.
VOLTAGE DISPLAY: This display shows:
-phase R voltage if the load is on mains
-Phase U voltage if the load is on the genset
By pressing the MENU key, below values may be displayed:
-(L1-L2-L3) mains phase to neutral voltages
-(L1-L2-L3) generator phase to neutral voltages
-(L12-L23-L31) mains phase to phase voltages
-(L12-L23-L31) generator phase to phase voltages
If the service counters group is displayed, then this display will show the counter name.
In programming mode it displays (PGM).
CURRENT DISPLAY: This display will show the current values measured using the current
transformers. Using the programming menu, current transformers within the range of 10/5A to 9000/5A
may be programmed.
In programming mode it displays the program number.
MULTIFUNCTION DISPLAYS: By pressing the MENU key below values may read:
-generator frequency (Hz)
-generator active power (KW)
-engine rpm
-fuel level
-oil temperature
-battery voltage (V-DC),
In programming mode it displays the program value.