Figure 13. Customer input power outlet, three-phase
Single-phase power
Each PowerBrick in a PowerMax 2000 system on single-phase power is powered by a separate line cord. Each line cord energizes the
circuit breakers and corresponding PDU outlets, as follows:
Table 27. PowerMax 2000 line cord and jumper configurations, single-phase
PowerBrick Components Line cord
location
Jumper location
(from/to)
Circuit breakers PDU outlets
PowerBrick 2
(Upper System)
DAE 4 P6 No additional power
jumpers required
11-12 31-37
DAE 3
SPS 2A/2B
PowerBrick 1
(Upper System)
DAE 2 P4 J4<>P5
PN: 038-004-186
This jumper must be
installed in the field with
a second system.
7-10 19-30
DAE 1
SPS 3A/3B
PowerBrick 2
(Lower System)
DAE 4 P3 No additional power
jumpers required
5-6 13-18
DAE 3
SPS 2A/2B
PowerBrick 1
(Lower System)
DAE 2 P1 J1<>P2
PN: 038-004-186
This jumper is pre-
installed at the factory
and should not be
removed.
1-4 1-12
DAE 1
SPS 3A/3B
40 Power Cabling, Cords and Connectors