Figure 14. Customer input power outlet, single-phase
PowerMax 8000 line cord and jumper
configurations
Three-phase power
A PowerMax 8000 system bay on three-phase power requires a line cord in outlet P1 and a power jumper from J1 to P2. The jumper, PN
038-004-435 (3-phase DELTA) or PN 038-004-481 (3-phase WYE), is pre-installed at the factory and should not be removed.
Table 28. PowerMax 8000 line cord configurations, three-phase
PowerBrick Components Line cord location
PowerBrick 4/8 DAE 6 No additional line cords required
SPS 4A/4B
PowerBrick 3/7 DAE 5 No additional line cords required
DAE 4
SPS 3A/3B
PowerBrick 2/6 DAE 3 No additional line cords required
SPS 2A/2B
PowerBrick 1/5 DAE 2 P1
DAE 1
MIBE A/B (PowerBrick 1 ONLY)
Ethernet switch A/B (PowerBrick 1 ONLY)
SPS 1A/1B
Power Cabling, Cords and Connectors 41