Table 46. PDU label location, third-party racks
Product Location
PowerMax 2000 HERC ENG 1 PBRICK 3RD PTY INSTALL KIT
PN 106-887-303
PowerMax 8000 ENGINE 1 3RD PTY PBRICK ZEUS
PN 106-887-268
Applying PDU labels
Steps
1. For each bay, locate and complete each PDU label. If necessary, modify the line cord numbers to match your configuration.
NOTE: For three-phase power, enter data only in the first column.
2. Place each label on the rear cabinet sidewall for side A and B.
Figure 36. PDU label , single-phase and three-phase
3. For third-party racks, do one of the following:
For three-phase power: Using plastic ties, attach the PDU connection tag to the main AC power cable connected to zone A and B.
Place the label close to the plug but on the side of the rack where it will not interfere with any rails.
For single-phase power: Using plastic ties, attach the PDU connection tag to the P1 AC power cable connected to zone A and B.
Place the label close to the plug but on the side of the rack where it will not interfere with any rails.
AC power specifications
Table 47. Input power requirements - Single-phase, North American, International, Australian
Specification North American 3-wire connection
(2 L & 1 G)
a
International and Australian 3-wire
connection
(1 L & 1 N & 1 G)
a
Input nominal voltage 200–240 VAC ± 10% L- L nom 220–240 VAC ± 10% L- N nom
Frequency 50–60 Hz 50–60 Hz
Circuit breakers 30 A 32 A
Power zones Two Two
70 Best Practices for AC Power Connections