Physical — Enclosure
Height 44.0 cm (17.3 inch)
Width 44.7 cm (17.6 inch)
Depth 75.5 cm (29.7 inch)
Weight (maximum) 200.5 kg (442 lb)
Weight (empty) 44.6 kg (98.1 lb)
Environmental
NOTE: For additional information about environmental measurements for specific system configurations, see
dell.com/environmental_datasheets.
Temperature
Maximum Temperature Gradient (Operating and
Storage)
20 °C/h (36 °F/h)
Storage Temperature Limits –40 °C to 65 °C (–40 °F to 149 °F)
Temperature (Continuous Operation)
Temperature Ranges (for altitude less than 950 m or
3117 ft)
10 °C to 35 °C (50 °F to 95 °F) with no direct sunlight on
the equipment.
Humidity Percentage Range 10% to 80% Relative Humidity with 26 °C (78.8 °F)
maximum dew point.
Relative Humidity
Storage 5% to 95% RH with 33 °C (91 °F) maximum dew point.
Atmosphere must be non-condensing at all times.
Maximum Vibration
Operating 0.26 G
rms
at 5 Hz to 350 Hz (all operation orientations).
Storage 1.87 G
rms
at 10 Hz to 500 Hz for 15 min (all six sides
tested).
Maximum Shock
Operating One shock pulse in the positive z axis of 31 G for 2.6 ms in
all operational orientations.
Storage Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of
the system) of 71 G for up to 2 ms.
Maximum Altitude
Operating
3048 m (10,000 ft).
Storage 12,000 m (39,370 ft).
Operating Altitude De-rating
Up to 35 °C (95 °F) Maximum temperature is reduced by 1 °C/300 m (1 °F/547
ft) above 950 m (3,117 ft).
35 °C to 40 °C (95 °F to 104 °F) Maximum temperature is reduced by 1 °C/175 m (1 °F/319
ft) above 950 m (3,117 ft).