45 PowerEdge R420 Technical Guide
Resolution Refresh Rate (Hz) Color Depth (bit)
1152 x 864 60, 75, 85 8, 16, 32
1280 x 1024 60, 75 8, 16, 32
Environmental specifications
Table 26 details the environmental specifications for the R420. For additional information about
environmental measurements for specific system configurations, see
Dell.com/environmental_datasheets
.
Table 26. Environmental specifications
Fresh Air: temperature, humidity, altitude de-rating
Continuous
operation
10°C to 3C (50°F to 95°F) at 10% to 80% relative humidity with 26°C (78.8°F) maximum
dew point (maximum wet bulb temperature). De- rate maximum allowable dry bulb
temperature at 1°C per 300m above 950m (1°F per 547 ft above 3117 ft).
Expanded
operation
When operating in the expanded temperature range, system performance may be impacted,
and ambient temperature warnings may be reported on the LCD and in the System Event
Log.
≤ 10% of annual operating hours: C to 10°C and 35°C to 40°C (with no direct sunlight on
the equipment) at 5% to 85% relative humidity with 26°C dew point (maximum wet bulb
temperature). Outside the standard operating temperature (10°C to 35°C), the system can
operate down to 5°C or up to 40°C for a maximum of 10% of its annual operating hours. For
temperatures between 3C and 40°C (95°F to 104°F), de- rate maximum allowable dry bulb
temperature by 1°C per 175m above 950m (1°F per 319 ft above 3117 ft).
≤ 1% of annual operating hours: 5°C to 5°C and 40°C to 45°C (with no direct sunlight on
the equipment) at 5% to 90% relative humidity with 26°C dew point (maximum wet bulb
temperature). Outside the standard operating temperature (10°C to 35°C), the system can
operate down to 5°C or up to 45°C for a maximum of 1% of its annual operating hours. For
temperatures between 4C and 45°C (104°F to 113°F), de-
rate maximum allowable dry bulb
temperature by 1°C per 125m above 950m (1°F per 228 ft above 3117 ft).
Expanded operation restrictions:
No cold startup below 5°C
Maximum altitude for the operating temperature must be 3050m (10,000ft)
Redundant power supplies required
Temperature
Operating See Fresh Air for temperature information
Storage 40
o
C to 65
o
C (- 40
o
F to 149
o
F) with a maximum temperature gradation of 20
o
C per hour
Relative humidity
Operating See Fresh Air for relative humidity information
Storage 5% to 95% at a maximum wet bulb temperature of 33°C (91°F); atmosphere must be
condensing at all times
Maximum vibration
Operating 0.26 Grms at 5Hz to 350Hz in all orientations
Storage 1.87 Grms at 10Hz to 500Hz for 15 minutes (all six sides tested)

Table of Contents

Other manuals for Dell PowerEdge PDU Managed LED

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dell PowerEdge PDU Managed LED and is the answer not in the manual?

Dell PowerEdge PDU Managed LED Specifications

General IconGeneral
BrandDell
ModelPowerEdge PDU Managed LED
CategoryServer
LanguageEnglish

Related product manuals