Error! No text of specified style in document. DNT-T103 (Rev 4.1) Installation Guide
Boards
segment. Ensure you do not overlook this in laying out your network architecture.
LINKnet: Jumper select a termination resistor on each end of the network when there
are more than 2 nodes. Termination resistors do not need to be installed for one or two
nodes.
Repeater
MS/TP: A repeater (RPT-768) is not necessary unless more than 50 nodes will be installed
on a network
or you need to extend the network beyond 4000 ft (1220 m).
LINKnet: Repeaters should not be necessary. Ensure the maximum distance is no
more than 1000 ft (300 m).
For more information refer to the Delta Controls Wiring and Installation Guidelines.