Chapter 5 Parameters|VFD-S Series
5-50 Revision August 2006, SE08, SW V2.61
Example 5 (Pr. 5-07 = d1 Execute one cycle of the PLC program):
In this example, the PLC program runs continuously. It should be noted that the times of reserve
motion may be shorter than expected, due to the acceleration/deceleration times.
Frequenc
y
60Hz
50Hz
40Hz
30Hz
20Hz
15Hz
10Hz
0Hz
Time
(Sec)
FWD
REV
5-09
Master freq.=5Hz
5-00=10 Hz
5-01=20 Hz
5-02=40 Hz
5-03=60 Hz
5-04=50 Hz
5-05=30 Hz
5-06=15 Hz
4-07=d17
3-05=d10
3-06=d11
5-07=d1
5-08=d68
5-09=10
5-10=10
5-11=12
5-12
Sec
Sec
Sec
=15 Sec
5-13=15 Sec
5-14=8 Sec
5-15=17 Sec
5-16=17 Sec
* The calculation of time for Pr.5-11, Pr.5-12, Pr.5-15 and Pr.5-16 should be carefully planned.
5-08 PLC Forward/Reverse Motion Unit: 1
Settings d0 to d255 Factory Setting: d0
This parameter controls the direction of motion for the Multi-Step Speed Pr.5-00 to Pr.5-06
and the Master Frequency. The original direction of Master Frequency will become invalid.
NOTE
The equivalent 8-bit number is used to program the forward/reverse motion for each of the 8 speed
steps (including Master Frequency). The binary notation for the 8-bit number must be translated into
decimal notation and then be entered.
1234567
Weights
Bit
0=Forward
1=Reverse
Direction of 1st Pr.5-00 speed for
Direction of 2nd Pr.5-01 speed for
Direction of 3rd Pr.5-02 speed for
Direction of 4th Pr.5-03 speed for
Direction of 5 Pr.5-04th speed for
Direction of 6 Pr.5-05th speed for
Direction of 7 Pr.5-06th speed for
0
Director of Master Frequency during PLC