EasyManuals Logo

Delta Electronics AC Motor Drive VFD007S23A User Manual

Delta Electronics AC Motor Drive VFD007S23A
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #166 background imageLoading...
Page #166 background image
Appendix B Accessories|VFD-S Series
Revision August 2006, SE08, SW V2.61 B-11
460V, 50/60Hz, 3-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max.
continuous
Amps
3% impedance 5% impedance
0.4 1/2 2 3 20 32
0.75 1 4 6 9 12
1.5 2 4 6 6.5 9
2.2 3 8 12 5 7.5
B.3.2 AC Output Reactor Recommended Value
115V/230V, 50/60Hz, 3-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max.
continuous
Amps
3% impedance 5% impedance
0.2
1/4 4 4 9 12
0.4
1/2 6 6 6.5 9
0.75
1 8 12 3
5
1.5
2 8 12 1.5
3
2.2
3 12 18 1.25
2.5
460V, 50/60Hz, 3-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max.
continuous
Amps
3% impedance 5% impedance
0.4 1/2 2 3 20 32
0.75
1
4 6 9 12
1.5
2
4 6 6.5 9
2.2
3
8 12 5 7.5
B.3.3 Applications for AC Reactor
Connected in input circuit
Application 1
Question
When more than one AC motor drive is
connected to the same mains power, and one
of them is ON during operation.
When applying power to one of the AC motor
drive, the charge current of the capacitors
ma
y
cause volta
g
e di
p
. The AC motor drive

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Electronics AC Motor Drive VFD007S23A and is the answer not in the manual?

Delta Electronics AC Motor Drive VFD007S23A Specifications

General IconGeneral
BrandDelta Electronics
ModelAC Motor Drive VFD007S23A
CategoryNetwork Card
LanguageEnglish

Related product manuals