EasyManua.ls Logo

Delta Electronics AC Motor Drive VFD007S23A - Page 126

Delta Electronics AC Motor Drive VFD007S23A
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5 Parameters|VFD-S Series
Revision August 2006, SE08, SW V2.61 5-71
Content Address Functions
Bit 0-1 00: No function
01: Stop
10: Run
11: Jog + Run
Bit 2-3 Not used
Bit 4-5
00: No function
01: FWD
10: REV
11: Change direction
2000H
Bit 6-15 Not used
2001H Freq. command
Bit 0 1: EF (external fault) on
Bit 1 1: Reset
Command
2002H
Bit 2-15 Not used
Status
monitor
Read only
2100H Error code:
0: No errors occurred
1: Over-current (oc)
2: Over-voltage (ov)
3: Overheat (oH)
5: Overload1 (oL1)
6: External fault (EF)
7: Not used
8: Not used
9: Current exceeds 2 times rated current during acceleration
(ocA)
10: Current exceeds 2 times rated current during deceleration
(ocd)
11: Current exceeds 2 times rated current during steady state
operation (ocn)
12: Ground Fault (GF)
13: Reserved
14: Low voltage (Lv)
15: CPU failure 1 (cF1)
16: CPU failure 2 (cF2)
17: Base block
18: Overload (oL2)
19: Auto acceleration/deceleration failure (cFA)
20: Software protection enable (codE)
21: Reserved
22: CPU failure (cF3.1)
23: CPU failure (cF3.2)
24: CPU failure (cF3.3)
25: CPU failure (cF3.4)
26: CPU failure (cF3.5)
27: CPU failure (cF3.6)
28: CPU failure (cF3.7)
29: Hardware protection failure (HPF.1)
30: Hardware protection failure (HPF.2)
31: Hardware protection failure (HPF.3)
32: CE 10
33: Reserved
34: Software error (SErr)

Table of Contents