EasyManua.ls Logo

Delta Electronics AC Motor Drive VFD007S23A

Delta Electronics AC Motor Drive VFD007S23A
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5 Parameters|VFD-S Series
Revision August 2006, SE08, SW V2.61 5-3
Pr. Explanation Settings
Factory
Setting
NOTE
460V series: d4.0V to d510V d24
1-05 Minimum Output Frequency (Fmin) d1.0 to d60.0 Hz d1.0
230V series: d2.0V to d255V d12.0
1-06
Minimum Output Voltage (Vmin)
460V series: d4.0V to d510V d24.0
1-07 Output Frequency Upper Limit d1 to d110% d100
1-08 Output Frequency Lower Limit d0 to d100% d0
1-09 Accel Time 1 d0.1 to d600 Sec d10.0
1-10 Decel Time 1 d0.1 to d600 Sec d10.0
1-11 Accel Time 2 d0.1 to d600 Sec d10.0
1-12 Decel Time 2 d0.1 to d600 Sec d10.0
1-13 Jog Acceleration / Deceleration Time d0.1 to d600 Sec d10.0
1-14 Jog Frequency d1.0 Hz to d400 Hz d6.0
1-15
Auto acceleration / deceleration (refer
to Accel/Decel time setting)
d0: Linear Accel/Decel
d1: Auto Accel, Linear Decel
d2: Linear Accel, Auto Decel
d3: Auto Accel/Decel (Set by load)
d4: Linear Accel; Auto Decel, Stall
Prevention during Decel
d5: Auto Accel/Decel, Stall
Prevention during Decel
d0
1-16 Acceleration S-Curve d0 to d7 d0
1-17 Deceleration S-Curve d0 to d7 d0
1-18 Jog Decelerating Time
d0.0 Jog Decelerating Time
Determined by Pr.1-13
d0.1 to d600
d0.0
Group 2 Operation Method Parameters
Pr. Explanation Settings
Factory
Setting
NOTE
2-00
Source of Master Frequency
Command
d0: Master Frequency input
determined by digital keypad.
(record the frequency of power
loss and it can do analog
overlap plus)
d1: Master Frequency determined
by analog signal DC 0V-10V
(external terminal AVI). (won’t
record the frequency of power
loss and it can’t do analog
overlap plus)
d2: Master Frequency determined
by analog signal DC 4mA -
20mA (external terminal AVI).
(won’t record the frequency of
power loss and it can’t do
analog overlap plus)
d3: Master Frequency determined
by Potentiometer on the digital
keypad. (won’t record the
frequency of power loss and it
can do analog overlap plus)
d0

Table of Contents

Related product manuals