EasyManua.ls Logo

Delta Electronics AC Motor Drive VFD007S23A - Page 97

Delta Electronics AC Motor Drive VFD007S23A
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5 Parameters|VFD-S Series
5-42 Revision August 2006, SE08, SW V2.61
Frequency
Master Frequency
Acceleration
inhibit
Acceleration
inhibit
Actual operation frequency
Deceleration
inhibit
Deceleration
inhibit
Time
Mx-GND
Operation
command
ON ON
ON ON
ON
OFF
d12 First or Second Acceleration/Deceleration Time Selection:
Parameter value d12 programs a Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3
(Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) to control selection of First or Second
Acceleration/deceleration time. (Refer to Pr.1-09 to Pr.1-12.)
GND
Mx "Close": 2nd Acceleration/Deceleraion
Mx set d12
"Open": 1st Acceleration/Deceleration
Frequency
Master
Frequency
Pr.
1-09
1st
A
cceleration/
Deceleration
2nd
A
cceleration/
Deceleration
1st
Acceleration
Pr.
1-10
Pr.
1-12
Pr.
1-12
2nd
Deceleration
Time
Mx-GND
operation
command
ON
ON
ON
ON
ON
OFF
Pr.
1-11
Pr.
1-09
d13, d14 External Base Block:
Parameter values d13, d14 program Multi-Function Input Terminals: M1 (Pr.4-04), M2 (Pr.4-05), M3
(Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) for external Base Block control. Value d13 is for normally
open (N.O.) input, and value d14 is for a normally closed (N.C.) input.