DELTALA Installation http://www.deltala.com/installa.htm
1 of 7 10/24/2007 9:23 AM
P.O. BOX 750 BIG SPRING, TX 79721 (432) 267-1000
INSTALLATION
If there is a surge so strong that something must be damaged, we prefer that our arrestor be
damaged rather than your equipment. Since we expect the arrestor might be damaged,
install it in a regular electrical enclosure to protect personnel from accidental contact with live
parts. Should the arrestor be damaged, it will not damage other components in the box. If the
arrestor cannot be placed in an enclosure, consider using our vent valve model. Its case will
not rupture. A small vent on the bottom of the case will open.
To protect a submersible pump motor, connect the black wires to the line terminals and the
white wire to the casing and/or tubing.
To protect equipment on a radio tower or a drilling rig, mount the arrestor to a junction box at
the bottom of each string of lights going up to the tower. Connect the black leads to the
circuit conductors and the white wire to the rig steel. Arrange for the conductors feeding the
junction box to be parallel with the earth. Connect an arrestor to the generator leads
grounding the white wire to the generator frame. Connect an arrestor to each lighting panel
connecting black wires to the circuit conductors, and the white wire to the box and rig frame.
To protect a house, the arrestor should be mounted on an outside switch or junction box, or
in the breaker box. The black wires should be connected to the circuit. The white wire should
be connected to the neutral, the box, and/or a solid ground. Model numbers G have a
separate ground wire.
To protect electronic equipment such as computers, transmitters, receivers, etc., connect the
black wires to the terminals of the device and the white wire to chassis. Mount the arrestor in
the cabinet. Consider using a surge capacitor connected to the breaker feeding them.
To protect a watt-hour meter, connect the black wires to the line terminals, and the white wire
to the meter box.
To protect an electric motor on machinery, connect the black wires to the motor leads and
the white wire to the motor frame.
Where the switch and motor are within six feet of each other, one arrestor will protect both
provided a solid ground wire is fastened to the switch box, motor frame, and arrestor white
wire. However, optimum protection is afforded only when the arrestor is connected directly to
the device to be protected.
To protect a motor control switch separately, connect the black wires to the line terminals
Home General Products Ordering Service/Inquiry Form Downloadable Specs Site Map
Question and Answer IconNeed help?

Do you have a question about the Delta LA302R and is the answer not in the manual?

Delta LA302R Specifications

General IconGeneral
ModelLA302R
TypeSurge Protector
Wire Size14 AWG
MountingWall Mount
Response TimeLess than 1 nanosecond
Frequency50/60 Hz

Summary

Installation Procedures

General Installation and Enclosure

Install arrestor in an electrical enclosure for personnel protection and to prevent damage during surges.

Application-Specific Wiring

Connect arrestors for submersible pumps, towers, houses, electronics, meters, and motors as specified.

Product Guarantee

Warranty Details

Arrestor is guaranteed against defects; damage from surges over 60,000 amps is expected.

Model-Specific Installation

LA302R, LA302, CA302R Installation

Wiring instructions and diagram for LA302R, LA302, CA302R models in a three-phase system.

Safety Warnings

Electrical work is dangerous; only experienced persons should perform installations.

Common Installation Modes

Installation Mode 1: Weather Head

Secure arrestor in weather head using an ell bracket or strap.

Installation Mode 2: Meter Box

Secure meter box wiring using an ell bracket or strap, connecting white wire to neutral.

Installation Mode 3: Neutral Connection

Connect white wire to neutral using a locknut for secure attachment.

Installation Mode 4: Main Box

Secure main box wiring using an ell bracket or strap.