1 WARNING
Please carefully read this instruction before using the TP04G.
DANGER! DC input power must be OFF before any maintenance. Do not insert or remove wires and
connectors while power is applied to the circuit. Only the qualified technicians are allowed to perform the
maintenance.
The TP04G display panel is waterproof. But please prevent grease, corrosive liquids and sharp objects from
contacting the TP04G.
DANGER! The TP04G requires 24VDC input power. The 24VDC input power should not be connected to
the RS-485 communication port. The unit may be destroyed or can’t be repaired if the input power is
improperly applied. Please always check the correctly input power wiring before apply power.
DANGER! An electrical charge will remain on the DC-link capacitors for 1 minute after power OFF. This
residual power may be hazardous and the TP04G should not be worked on until this charge has dissipated.
To prevent injury, do not conduct any wiring or investigation on the TP04G until 1 minute after power has
been removed.
CAUTION! Always ground the TP04G by using the grounding terminal. Not only this acts as a safety, but
also filter out electrical noise. The ground method must comply with the laws of the country where the unit is
to be installed.
CAUTION! TP04G may be damaged if the fixed support (shipped with the pack) is adjusted too tight.
Battery replacement: please use UL component type: CR2030 lithium battery which battery life is 1200
hours after power loss. (NOTE: RTC should be reset after changing battery).
2 INTRODUCTION
2.1 Model Explanation
z Thank you for choosing DELTA TP Series. TP04G-AS2 has the features of high resolution 128*64 to display
8*4 Chinese characters max, and Multilanguage support.
z Built-in two communication ports so that RS-232 and RS-485/RS-422 can be used simultaneously.
z Built-in RTC and communication/alarm indication LED.
z Possess extension slot for program copy card to copy settings and programs rapidly and save download
time.
z Built-in various objects to meet your requirements.
Nameplate
MODEL :
POWER INPUT :
TP04GAS2W6050004
VX.XX
TP04G-AS2
24Vdc 3.5W
DE LTA ELE CTRONICS, INC M AD E IN XXXXX XX
Production model
Power input spec.
Barcode and
serial number
Version
Note: The words of “MADE IN XXXXX” will be different due to the manufacturing location.
Model and Serial Number Explanation
Model Explanation
TP 04 G AS 2 -
RS-232/RS-422/RS-485 interface
Reserved
T: Tex t mode
G: Graphic mode
LCD Spec.
Series name
Serial Number Explanation
TP04GAS 2 W 6 05 0004
Production serial number
Production weeks
Production year(2006)
Production plant(W:Wuijang)
Version
Production model
2.2 Outline
LCM
Display Area
RS-485/RS-422
Indication LED
Escape/Exit
Shift Key
Arrow keys
Function Keys
Enter key
RS-232 Indication LED
Alarm Indication LED
2.3 Panel Function Explanation
PANEL COMPONENT EXPLANATION
Alarm Indication LED (RED)
Status 1: When power is on, LED will blink slowly for three times.
Status 2: When there is an abnormal situation, LED will blink quickly along with
an alarm sound.
RS-232 Indication LED
(Yellow)
LED will blink when transmits program and communicates via RS-232.
RS-485/RS-422 Indication
LED (Green)
LED will blink when communicates via RS-485/RS-422.
LCM display Area Liquid Crystal Module display area used to display current program state.
Escape/Exit Used to cancel an incorrect input, or to Exit a programming step.
Arrow Keys
UP/Pg Up: Used to increase the value or move up one page.
Pg Dn/DOWN: Used to decrease the value or move down one page.
Left: Left direction key (move curser to left).
Right: Right direction key (move cursor to right).
Shift Key Used to select keys F5, F6, F7, F8, F9.
Enter key Used to input a value or accept a programming command.
Function Keys
F0/F5: used to be constant 0 (F0) and 5 (Shift+F0) when it is in the system
menu, user can use it to define functions separately when they are in
user page.
F1/F6: used to be constant 1 (F1) and 6 (Shift+F1) when it is in the system
menu, user can use it to define functions separately when they are in
user page.
F2/F7: used to be constant 2 (F2) and 7 (Shift+F2) when it is in the system
menu, user can use it to define functions separately when they are in
user page.
F3/F8: used to be constant 3 (F3) and 8 (Shift+F3) when it is in the system
menu, user can use it to define functions separately when they are in
user page.
F4/F9: used to be constant 4 (F4) and 9 (Shift+F4) when it is in the system
menu, user can use it to define functions separately when they are in
user page.
2.4 Back Panel
BATTERY
SWITCH OR
RS-485/422
5-PIN terminals: / Wire gauge: 12-24 AWG / Torque: 4.5 lb.-inch
2.5 Dimension
Front panel (unit: mm [inch]) Right side diagram (unit: mm [inch])
97.00
[3.82]
147.00 [5.79]
85.00
[3.35]
Back panel Mounting dimension (unit: mm [inch])
Thickness Range 0.5~9mm
135~136.5[5.31~5.37]
85
[3.35]
Vertical view (Unit: mm)
2.6 Installation
One easy way is insert TP04G to the opening hole of panel and tight up the screws. However, if a firm
mounting TP04G to the panel is needed, please use the fixed support accessory which is packed together with
TP04G, then infix the fixed support in the back and tight up the screws. (NOTE: the flat surface should be a Type 4
"Indoor Use Only" enclosure or equivalent.)
If fixed support is not installed well, Delta will not guarantee the waterproof function. If you turn the screw
exceeds torque: 4-5(kg-cm), TP04G could be damaged.
(Note:the flat surface shoud be a Type 4 “Indoor Use Only” enclosure or equivalent.)
Please leave sufficient space (more than 50mm) around the unit for heat dissipation.
Thickness:
0.5~9.0mm
50mm
50mm
Please leave sufficient space (more than 50mm)
around the unit for heat dissipation.
3 SPECIFICATION
3.1 Electrical Specification
ITEM TP04G-AS2
Function Key/Digital Key F0~F4, ESC, SHIFT, ENTER and ARROW keys
External Input Power 24V (-15%-20%) 3.5W Max.
Memory Capacity 256K Byte
CPU Hitachi HD64F3064F
RAM of System 32K Byte
Communication Interface COM1: RS232; COM2: RS485/RS422
Waterproof Class of Front Panel IP65/NEMA4/UL Type 4 (indoor use)
Environment Condition
0~50℃, relative humidity 20-90% RH (non-condensing)
Storage Temperature for Hardware
-20~60℃
Vibration 1.0G, 10-150Hz, X, Y, Z three directions and 10 sweep cycles per axis
Shock
15G, 11ms, from X, Y, Z three directions and three times for each
direction
Radiated Emission CISPR22, Class A
Electrostatic Discharge Immunity EN61000-4-2/1995
Radiated Immunity EN61000-4-31995
Electrical Fast Transient EN61000-4-4/1995
Weight/Dimension 0.24kg/147×97×35.5mm (Width × Height × Deep)
Cooling Method Natural Air Cooling
Pollution Degree 2
Altitude 2000 m or lower