Chapter 5 Parameters_VFD-B Series
Revision 10/2005, BE13, SW V4.08 5-53
Group 4: Input Function Parameters
04 - 00
aAVI Analog Input Bias Unit: 0.01
Settings 0.00 to 200.00% Factory Setting: 0.00
04 - 01
AVI Bias Polarity
Factory Setting: 00
Settings 00 Positive Bias
01 Negative Bias
04 - 02
aAVI Input Gain Unit: 1
Settings 1 to 200% Factory Setting: 100
04 - 03
AVI Negative Bias, Reverse Motion Enable/Disable
Factory Setting: 00
Settings 00 No AVI Negative Bias Command
01 Negative Bias: REV Motion Enabled
02 Negative Bias: REV Motion Disabled
04 - 11
aACI Analog Input Bias Unit: 0.01
Settings 0.00 to 200.00% Factory Setting: 0.00
04 - 12
ACI Bias Polarity
Factory Setting: 00
Settings 00 Positive Bias
01 Negative Bias
04 - 13
aACI Input Gain Unit: 1
Settings 01 to 200% Factory Setting: 100
04 - 14
ACI Negative Bias, Reverse Motion Enable/Disable
Factory Setting: 00
Settings 00 No ACI Negative Bias Command
01 Negative Bias: REV Motion Enabled
02 Negative Bias: REV Motion Disabled