Preface
Thank you for choosing DELTA’s high-performance VFD-M Series. The VFD-M Series is
manufactured with high-quality components and materials and incorporates the latest microprocessor
technology available.
Getting Started
This quick start will be helpful in the installation and parameter setting of the AC motor drives. To
guarantee safe operation of the equipment, read the following safety guidelines before
connecting power to the AC motor drives. For detail information, refer to the VFD-M User Manual
on the CD supplied with the drive.
DANGER!
1. AC input power must be disconnected before any wiring to the AC motor drive is made.
2. A charge may still remain in the DC-link capacitors with hazardous voltages, even if the power
has been turned off. To prevent personal injury, please ensure that power has turned off before
opening the AC motor drive and wait ten minutes for the capacitors to discharge to safe voltage
levels.
3. Never reassemble internal components or wiring.
4. The AC motor drive may be destroyed beyond repair if incorrect cables are connected to the
input/output terminals. Never connect the AC motor drive output terminals U/T1, V/T2, and
W/T3 directly to the AC mains circuit power supply.
5. Ground the VFD-M using the ground terminal. The grounding method must comply with the laws
of the country where the AC motor drive is to be installed. Refer to the Basic Wiring Diagram.
6. VFD-M series is used only to control variable speed of 3-phase induction motors, NOT for 1-
phase motors or other purpose.
7. VFD-M series shall NOT be used for life support equipment or any life safety situation.
WARNING!
1. DO NOT use Hi-pot test for internal components. The semi-conductor used in AC motor drive
easily damage by high-pressure.
2. There are highly sensitive MOS components on the printed circuit boards. These components
are especially sensitive to static electricity. To prevent damage to these components, do not
touch these components or the circuit boards with metal objects or your bare hands.
3. Only quality person is allowed to install, wire and maintain AC motor drive.
CAUTION!
1. Some parameters settings can cause the motor to run immediately after applying power.
2. DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight,
high humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic
particles.
3. Only use AC motor drives within specification. Failure to comply may result in fire, explosion or
electric shock.
4. To prevent personal injury, please keep children and unqualified people away from the
equipment.
5. When the motor cable between AC motor drive and motor is too long, the layer insulation of the
motor may be damaged. Please use a frequency inverter duty motor or add an AC output
reactor to prevent damage to the motor. Refer to appendix B Reactor for details.
6. The rated voltage for AC motor drive must be 240V for 230V models (120V for 115V models,
480V for 460V models, 600V for 575V models) and the mains supply current capacity must
be 5000A RMS (10000A RMS for the 40hp (30kW) models).
Question and Answer IconNeed help?

Do you have a question about the Delta VFD015M21A and is the answer not in the manual?

Delta VFD015M21A Specifications

General IconGeneral
ModelVFD015M21A
Horsepower2 HP
Rated Output Current6.5A
Control MethodV/F Control
Protection LevelIP20
Weight1.5 kg
Input Voltage220V
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating
SeriesDelta VFD-M

Summary

Getting Started

Safety Precautions

Essential safety guidelines including DANGER, WARNING, and CAUTION notices for safe operation.

Specifications

115V Class Specifications

Technical specifications for the 115V Class VFD-M series drives, covering input/output ratings and performance.

230V Class Specifications

Technical specifications for the 230V Class VFD-M series drives, covering input/output ratings and performance.

575V Class Specifications

Control Characteristics

General Specifications

Control System

Details on the control system, frequency setting resolution, output frequency, and torque characteristics.

Operating Characteristics

Describes operational features like overload endurance, skip frequency, accel/decel time, and V/F patterns.

Environmental Conditions

Basic Wiring Diagram

Description of Digital Keypad

How to Operate the Digital Keypad LC-M02E

Step-by-step guide on operating the digital keypad for selection, parameter setting, and modification.

Power Terminals

Terminal Explanations

Control Terminal Wiring (Factory Setting)

Factory default wiring configurations for control terminals, including NPN mode with and without external power.

Factory Settings (NPN mode)

Details on factory settings for multi-function inputs, outputs, and analog signal terminals for NPN mode.

SUMMARY OF PARAMETER SETTINGS

Fault Codes

Dimensions

Related product manuals