Chapter 11 Summary of Parameter SettingsCP2000
11-24
Pr. Parameter Name Setting Range Default
06-06
Over-torque detection selection
(OT1)
0: No function
1: Continue operation after over-torque detection
during constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection
during RUN
4: Stop after over-torque detection during RUN
0
06-07 Over-torque detection level (OT1)
10–200% (100% corresponds to the light-load rated
current of the drive)
120
06-08 Over-torque detection time (OT1) 0.0–60.0 sec. 0.1
06-09
Over-torque detection selection
(OT2)
0: No function
1: Continue operation after over-torque detection
during constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection
during RUN
4: Stop after over-torque detection during RUN
0
06-10 Over-torque detection level (OT2)
10–200% (100% corresponds to the light-load rated
current of the drive)
120
06-11 Over-torque detection time (OT2) 0.0–60.0 sec. 0.1
06-13
Electronic thermal relay selection
1 (Motor 1)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disable
2
06-14
Electronic thermal relay action
time 1 (Motor 1)
30.0–600.0 sec. 60.0
06-15
Temperature level over-heat (OH)
warning
0.0–110.0°C 105.0
06-16
Stall prevention limit level
(Weak magnetic area current stall
prevention level)
0–100% (Pr.06-03, Pr.06-04) 50
06-17 Fault record 1 0: No fault record 0
06-18 Fault record 2 1: Over-current during acceleration (ocA) 0
06-19 Fault record 3 2: Over-current during deceleration (ocd) 0
06-20 Fault record 4 3: Over-current during constant speed (ocn) 0
06-21 Fault record 5 4: Ground fault (GFF) 0
06-22 Fault record 6 5: IGBT short-circuit (occ) 0
6: Over-current at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration (LvA)
12: Low-voltage during deceleration (Lvd)
13: Low-voltage during constant speed (Lvn)
14: Low-voltage at stop (LvS)
15: Phase loss protection (OrP)