English-1
Preface
Thank you for choosing DELTA’s high-performance VFD-M Series. The VFD-M Series is
manufactured with high-quality components and materials and incorporates the latest microprocessor
technology available.
Getting Started
This quick start will be helpful in the installation and parameter setting of the AC motor drives. To
guarantee safe operation of the equipment, read the following safety guidelines before
connecting power to the AC motor drives. For detail information, refer to the VFD-M User Manual
on the CD supplied with the drive.
DANGER!
1. AC input power must be disconnected before any wiring to the AC motor drive is made.
2. A charge may still remain in the DC-link capacitors with hazardous voltages, even if the power
has been turned off. To prevent personal injury, please ensure that power has turned off before
opening the AC motor drive and wait ten minutes for the capacitors to discharge to safe voltage
levels.
3. Never reassemble internal components or wiring.
4. The AC motor drive may be destroyed beyond repair if incorrect cables are connected to the
input/output terminals. Never connect the AC motor drive output terminals U/T1, V/T2, and
W/T3 directly to the AC mains circuit power supply.
5. Ground the VFD-M using the ground terminal. The grounding method must comply with the laws
of the country where the AC motor drive is to be installed. Refer to the Basic Wiring Diagram.
6. VFD-M series is used only to control variable speed of 3-phase induction motors, NOT for 1-
phase motors or other purpose.
7. VFD-M series shall NOT be used for life support equipment or any life safety situation.
WARNING!
1. DO NOT use Hi-pot test for internal components. The semi-conductor used in AC motor drive
easily damage by high-pressure.
2. There are highly sensitive MOS components on the printed circuit boards. These components
are especially sensitive to static electricity. To prevent damage to these components, do not
touch these components or the circuit boards with metal objects or your bare hands.
3. Only quality person is allowed to install, wire and maintain AC motor drive.
CAUTION!
1. Some parameters settings can cause the motor to run immediately after applying power.
2. DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight,
high humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic
particles.
3. Only use AC motor drives within specification. Failure to comply may result in fire, explosion or
electric shock.
4. To prevent personal injury, please keep children and unqualified people away from the
equipment.
5. When the motor cable between AC motor drive and motor is too long, the layer insulation of the
motor may be damaged. Please use a frequency inverter duty motor or add an AC output
reactor to prevent damage to the motor. Refer to appendix B Reactor for details.
6. The rated voltage for AC motor drive must be 240V for 230V models (120V for 115V models,
480V for 460V models, 600V for 575V models) and the mains supply current capacity must
be 5000A RMS (10000A RMS for the 40hp (30kW) models).
Question and Answer IconNeed help?

Do you have a question about the Delta VFD075M43A and is the answer not in the manual?

Delta VFD075M43A Specifications

General IconGeneral
ModelVFD075M43A
Power Rating7.5 kW
Horsepower10 HP
Input Phase3-phase
Control MethodV/f control, Sensorless vector control
IP RatingIP20
SeriesDelta VFD-M
Frequency Range0-400 Hz
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature, Short Circuit
Communication InterfaceRS-485
Cooling MethodFan Cooling
Operating Temperature-10°C to 50°C
Storage Temperature-20 to 60 °C
Humidity5-95% (Non-condensing)
Altitude1000m

Summary

Specifications

115V Class Specifications

Technical specifications for 115V class VFD-M series models.

230V Class Specifications

Technical specifications for 230V class VFD-M series models.

460V Class Specifications

Technical specifications for 460V class VFD-M series models.

Basic Wiring Diagram

Main Circuit and Control Wiring

Illustrates the main power and control circuit connections for the VFD-M drive.

Digital Keypad Operation

Keypad Components and Usage Guide

Explains keypad parts and provides instructions for operation and parameter setting.

SUMMARY OF PARAMETER SETTINGS

Frequency, Operation Command, and Speed

Settings for frequency source, operation command, and speed parameters.

Parameter Settings: Stall Prevention & Braking

Parameter Settings: Faults & PLC

Parameter Settings: Control Modes & PID

Parameter Settings: PID Control & Sleep Modes

Fault Codes and Descriptions

Over Current, Over Voltage, and Overheating Faults

Causes and corrective actions for over current, over voltage, and overheating faults.

Low Voltage and Overload Faults

Details corrective actions for low voltage and overload fault conditions.

Fault Descriptions: Operational Issues

Over-current During Operation Phases

Discusses over-current faults during acceleration, deceleration, and steady state.

External Faults and Communication Errors

Covers corrective actions for external faults and communication errors.

Fault Codes: Hardware & Software Issues

Hardware Errors, Phase Loss, and Software Protection

Addresses hardware errors, phase loss, and software protection failures.