EasyManua.ls Logo

Delta VFD037CP43B-21

Delta VFD037CP43B-21
868 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter SettingsCP2000
12.1-12-18
When the minimum operation time (Pr.12-27=1) is enabled, the drive sorts the operation hours
according to the amount of running motors at the moment, and then choose the motor that has
the minimum operation hour to start after RUN command.
As Example 1 below shows, the drive starts Motor 2, which having a minimum operation time
among all eight motors.
As Example 2 below shows, Motor 8 does not start though it has the minimum operation time,
because only Motor 1 to Motor 5 are started. Moreover, if more than one motors have the same
minimum operation hour, the number of the motor takes the priority. Therefore, Motor 3 starts
rather than Motor 5.
Motor operation time-Example 1
Motor No. / Motor Status Status Operating Hour Operating Min./ Sec.
Motor 1 ON 0 59 59
Motor 2 ON 0 12 12
Motor 3 ON 2 00 00
Motor 4 ON 0 43 11
Motor 5 ON 1 33 00
Motor 6 ON 3 50 05
Motor 7 ON 1 05 22
Motor 8 ON 10 20 21
Motor operation time-Example 2
Motor No. / Motor status Status Operating Hour Operating Min./ Sec.
Motor 1 ON 0 59 59
Motor 2 ON 5 12 12
Motor 3 ON 0 33 00
Motor 4 ON 0 43 11
Motor 5 ON 0 33 00
Motor 6 OFF 3 50 05
Motor 7 OFF 1 05 22
Motor 8 OFF 0 00 01

Table of Contents

Related product manuals