EasyManua.ls Logo

Delta VFD037CP43B-21

Delta VFD037CP43B-21
868 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 17 Introduction to BACnet │CP2000
17-11
The Properties of Objects
Property ID
Object Type
Device Analog Value Binary Value
#4 ACTIVE TEXT V
#11 APDU_TIMEOUT V
#12 APPLICATION_SOFTWARE_VERSION V
#28 DESCRIPTION V V V
#30 DEVICE ADDRESS BINDING V V
#36 EVENT STATE V V
#44 FIRMWARE_REVISION V
#46 INACTIVE TEXT V
#62 MAX_APDU_LENGTH_ACCEPTED V
#63 MAX_INFO_FRAMES V
#64 MAX_MASTER V
#70 MODEL_NAME V
#73 NUMBER_OF_APDU_RETRIES V
#75 OBJECT_IDENTIFIER
V *1
V V
#76 OBJECT_LIST V
#77 OBJECT_NAME
V *1
V V
#79 OBJECT_TYPE V V V
#81 OUT OF SERVICE V V
#85 PRESENT VALUE
V *2 V *2
#87 PRIORITY ARRAY V *3 V *3
#96 PROTOCOL_OBJECT_TYPES_SUPPORTED V
#97 PROTOCOL_SERVICES_SUPPORTED V
#98 PROTOCOL_VERSION V
#104 RELINQUISH DEFAULT V *3 V *3
#107 SEGMENTATION_SUPPORTED V
#111 STATUS FLAGS V V
#112 SYSTEM_STATUS V
#117 UNITS V
#120 VENDOR_IDENTIFIER V
#121 VENDOR_NAME V
#139 PROTOCOL_REVISION V
#155 DATABASE_REVISION V
*1. The Object_ID and Object_Name Properties of Device are writeable.
*2. The Present_Value Property of some AV and BV objects are commandable.
*3. Only Commandable objects support Priority_Array and Relinquish_Default.

Table of Contents