Fault 
Name 
Fault Descriptions 
Corrective Actions 
 
 
Over-current during 
acceleration: 
1.  Short-circuit at motor 
output. 
2.  Torque boost too 
high. 
3.  Acceleration time too 
short. 
4.  AC drive output 
capacity is too small. 
 
1.  Check for possible poor insulation at the 
output line. 
2.  Decrease the torque boost setting in 
Pr.7-02. 
3.  Increase the acceleration time. 
4.  Replace the AC drive with one that has a 
higher output capacity (next HP size). 
 
Over-current during 
deceleration: 
1.  Short-circuit at motor 
output. 
2.  Deceleration time too 
short. 
3.  AC drive output 
capacity is too small. 
 
1.  Check for possible poor insulation at the 
output line. 
2.  Increase the deceleration time. 
3.  Replace with the AC drive with one that 
has a higher output capacity (next HP 
size). 
 
Over-current during 
steady state operation: 
1.  Short-circuit at motor 
output. 
2.  Sudden increase in 
motor loading. 
3.  AC drive output 
capacity is too small. 
1.  Check for possible poor insulation at the 
output line. 
2.  Check for possible motor stall. 
3.  Replace the AC drive with one that has a 
higher output capacity (next HP size). 
 
The external terminal 
EF-GND goes from OFF 
to ON. 
1.  When external terminal EF-GND is 
closed, the output will be turned off. 
(Under N.O.  E.F.) 
2.  Press RESET after fault has been 
cleared.