Chapter 10 Auto-tuning Process | VFD-ED 
 
 
NOTE: 
  In torque/vector control mode, do not run motors in parallel. 
  Do not use torque/vector control mode if the motor rated power exceeds the rated 
power for the AC motor drive. 
  The no-load current is usually 20–50% of the rated current. 
  The rated speed cannot be larger or equal to 120 f/p (f: output frequency Pr.01-01, p: 
Number of Motor Poles Pr.05-04). 
  After auto-tuning is finished, activate the drive again to make it operate when the auto-
tuning command source is the external terminal.