12 Descriptions of Parameter Settings | VFD-ED 
 
12: Low voltage during deceleration (Lvd)   
13: Low voltage during constant speed (Lvn) 
14: Low voltage at stop (LvS) 
15: Input Phase loss (PHL) 
  A minimum time interval between retries is 5.5 seconds when OCx/GFF faults are triggered. 
 
Frequency Command when the Most Recent Fault Occurred 
Control Mode
VF  VFPG  SVC  FOCPG    FOCPM    Default: Read only 
  Settings  0.00–655.35 Hz 
 
Output Frequency when the Most Recent Fault Occurred 
Control Mode
VF  VFPG  SVC  FOCPG    FOCPM    Default: Read only   
  Settings  0.00–655.35 Hz 
 
Output Current when the Most Recent Fault Occurred 
Control Mode
VF  VFPG  SVC  FOCPG    FOCPM    Default: Read only   
  Settings  0.00–655.35 Amps 
 
Motor Frequency when the Most Recent Fault Occurred 
Control Mode
VF  VFPG  SVC  FOCPG    FOCPM    Default: Read only   
  Settings  0.00–655.35 Hz 
 
Output Voltage when the Most Recent Fault Occurred 
Control Mode
VF  VFPG  SVC  FOCPG    FOCPM      Default: Read only   
  Settings  0.0–6553.5 V 
     
DC Bus Voltage when the Most Recent Fault Occurred 
Control Mode
VF  VFPG  SVC  FOCPG    FOCPM      Default: Read only   
  Settings  0.0–6553.5 V 
 
Output Power when the Most Recent Fault Occurred 
Control Mode
VF  VFPG  SVC  FOCPG    FOCPM      Default: Read only   
  Settings  0.0–6553.5 kW 
 
Output Torque when the Most Recent Fault Occurred 
Control Mode
VF  VFPG  SVC  FOCPG    FOCPM      Default: Read only   
DC Breaking
 
Malfunction
Pr06-52 
       Time interval of ttempting to econnect while malfunction
ar
Pr02-11~Pr02-16: 
MO
#46:  Malfunction Indication
RUN command (forward/reversly)
MI1 =40: Enable the motor drive
MO#12: Release the mechnical brake
MO #46:  Attempting to reconnect while malfunction
Auto Reset-
DC Breaking