Chapter 8 Option CardsMS300 
155 
 
Grounded installation 
  You must ground the option cards as listed below when wiring. The ground terminal is included in 
the option card package, as shown in Figure 8-20. 
1.  CMM-PD02 
2.  CMM-DN02 
3.  CMM-EIP02 
4.  CMM-EIP03 
5.  CMM-COP02   
6.  CMM-EC02 
7.  EMM-BPS02 
  Installation of the ground terminal:   
The B end of the grounding wire connects to the ground terminal block of the option card, as the 
No.6 shows in Figure 8-21 (see Chapter 8 for the ground terminal block position of other option 
cards). The A end of the grounding wire connects to the drive’s PE, as the circles show in Figure 8-
22 and Figure 8-23. 
 
Figure 8-21   
9 kg-cm/ (7.8 lb-in)/ (0.88 Nm) 
20 kg-cm/ (17.4 lb-in)/ (1.96 Nm) 
15 kg-cm/ (13.0 lb-in)/ (1.47 Nm) 
25 kg-cm/ (21.7 lb-in)/ (2.45 Nm) 
20 kg-cm/ (17.4 lb-in)/ (1.96 Nm) 
20 kg-cm/ (17.4 lb-in)/ (1.96 Nm)