Chapter 8 Option CardsMS300 
157 
 
Environment 
ESD (IEC 61800-5-1, IEC 6100-4-2) 
EFT (IEC 61800-5-1, IEC 6100-4-4) 
Surge Test (IEC 61800-5-1, IEC 6100-4-5) 
Conducted Susceptibility Test (IEC 61800-5-1, IEC 6100-4-6) 
Operation: -10–50ºC (temperature), 90% (humidity) 
Storage: -25–70ºC (temperature), 95% (humidity) 
Shock / Vibration 
Resistance 
International standards:   
IEC 61131-2, IEC 68-2-6 (TEST Fc) / IEC 61131-2 & IEC 68-2-27(TEST Ea) 
8-2-4 Installation 
PROFIBUS DP Connector 
Sending / receiving data P(B) 
Sending / receiving data N(A) 
8-2-5 LED Indicator & Troubleshooting 
There are two LED indicators on the CMM-PD02: POWER LED and NET LED. POWER LED displays 
the status of the working power. NET LED displays the connection status of the communication. 
POWER LED 
Power supply in normal status. 
Check if the connection between the CMM-PD02 
and the AC motor drive is normal. 
The CMM-PD02 is not connected to 
PROFIBUS DP bus. 
Connect the CMM-PD02 to the PROFIBUS DP bus. 
Invalid PROFIBUS communication 
address 
Set the PROFIBUS address of the CMM-PD02 
between 1–125 (decimal). 
The CMM-PD02 fails to 
communicate with the AC motor 
drive. 
Switch off the power and check whether the CMM-
PD02 is correctly installed and normally connected 
to the AC motor drive.