Chapter 12 Descriptions of Parameter SettingsMS300 
379 
 
The fourth error: ocA occurs after another 1000 minutes.   
The fifth error: ocd occurs after another 1000 minutes.   
The sixth error: ocn occurs after another 1000 minutes.   
Then, Pr.06-17–06-22 and Pr.06-63–06-70 are recorded as follows: 
NOTE: By examining the time record, you can see that the last fault (Pr.06-17) happened after 
the drive ran for four days and 240 minutes. 
Low Current Setting Level 
Low Current Detection Time   
0 : No function 
1 : Fault and coast to stop 
2 : Fault and ramp to stop by the second deceleration time   
3 : Warn and continue operation 
 The drive operates according to the setting for Pr.06-73 when the output current is lower than 
the setting for Pr.06-71 and when the time of the low current exceeds the detection time for 
Pr.06-72. Use this parameter with the external multi-function output terminal setting 44 (low 
current output).   
 The low current detection function does not execute when drive is in sleep or standby status.