Switch according to the deviation: 
  When the deviation absolute value between the set point and feedback is smaller than 
Pr.08-76 (PID2 Parameter Switch Deviation 1), the first group PID parameters are used. 
  When the deviation absolute value between the set point and feedback is larger than Pr.08-
77 (PID2 Parameter Switch Deviation 2), the second group PID parameters are used. 
  When the deviation absolute value between the set point and feedback is between Pr.08-76 
and Pr.08-77, the PID parameter is the linear interpolation value between the two PID 
parameter groups. 
 
 When Pr.08-78 is not set to 0, the allowed reverse running time after start-up is enabled. 
 When it is set to 1 second, the PID control is not allowed to change the running direction within 
0–1 seconds of starting time (Pr.08-21 = 0), and is allowed to change after 1 second of starting 
time (Pr.08-21 = 1).