Chapter 12 Descriptions of Parameter SettingsMS300 
417 
 
 There is a group of block transfer parameters available in the AC motor drive (Pr.09-11–Pr.09-
26). Using communication code 03H, you can store the parameters (Pr.09-11–Pr.09-26) that you 
want to read. 
 For example: according to the Address List (as shown in the table below), Pr.01-42 is shown as 
012A. Set Pr.09-11 to 012Ah (the minimum voltage of Pr.01-42 M2 is 2.0 V), and use Pr.09-11 
(communication address 090B) to read the communication parameter, the read value is 2.0.   
AC motor drive 
parameters 
GG is the parameter group, nn is the parameter number; 
for example, the address of Pr.04-10 is 040AH. 
 Mind if the block transfer parameters are read only. If the data is written to read-only parameters 
from the upper unit, a communication error may occur. 
Communication Decoding Method   
0: Decoding method 1 (20xx) 
1: Decoding method 2 (60xx) 
 EtherCAT card only supports decoding method 2 (60xx). 
Source of 
Operation 
Control   
Digital keypad controls the drive action regardless of decoding method 1 or 2. 
External terminal controls the drive action regardless of decoding method 1 or 
2. 
RS-485 controls the drive referring to index 2000h–20FFh   
Refer to index: 2020-01h–2020-FFh 
Refer to index:2060-01h–2060-FFh 
Refer to address: 2000h–20FFh 
Refer to address: 6000h–60FFh 
PLC command controls the drive action regardless of decoding method 1 or 2. 
NOTE: Refer to Section 15-4 CANopen Supported Index for the definition of 6000H.