Chapter 12 Descriptions of Parameter SettingsMS300 
424 
 
 
MI7 Single-Phase Pulse Input Stall Level 
 Determines the maximum MI7 single-phase pulse input feedback signal allowed before a fault 
occurs; the maximum operation frequency Pr.01-00 = 100%. 
Detection Time of MI7 Single-Phase Pulse Input Stall   
MI7 Single-Phase Pulse Input Stall Action 
0: Warn and continue operation 
1: Fault and ramp to stop 
2: Fault and coast to stop   
 When the drive output frequency exceeds the MI7 single-phase pulse input stall level (Pr.10-10), 
the drive starts to count the time. When the error time exceeds the MI7 single-phase pulse input 
stall detection time (Pr.10-11), the drive implements the MI7 single-phase pulse input stall action 
(Pr.10-12). 
MI7 Single-Phase Pulse Input Slip Range 
Detection Time of MI7 Single-Phase Pulse Input Slip 
MI7 Single-Phase Pulse Input Stall and Slip Error Action 
0: Warn and continue operation 
1: Fault and ramp to stop 
2: Fault and coast to stop   
 When the value of (rotation speed – motor frequency) exceeds the Pr.10-13 setting, and the 
detection time exceeds Pr.10-14; the drive starts to count the time. If the detection time exceeds 
Pr.10-14, the encoder feedback signal error occurs.