Impedance: 20 kΩ 
Range: 0–10 V / -10–10 V = 0–Maximum Operation 
Frequency (Pr.01-00) 
Mode switching by setting Pr.03-28 
AVI resolution = 11 bits (0–10 V) / 12 bits (-10–10 V) 
Impedance: Current mode=250 Ω, Voltage mode=20 kΩ 
Range: 0–20 mA / 4–20 mA / 0–10 V = 0–Maximum 
Operation Frequency (Pr.01-00)   
Mode switching by setting Pr. 03-29 
ACI resolution = 12 bits 
Switch: The AFM default is 0–10 V (voltage mode).   
To switch to the current mode, follow the 
instructions indicated on the inner side of the front 
cover or refer to page 2 of Chapter 6 in the user 
manual to switch AFM to the current mode position 
(0–20 mA / 4–20 mA) and set Pr.03-31. 
Voltage mode 
Range: 0–10 V (Pr.03-31 = 0) corresponds to the maximum 
operating range of the control target 
Max. output current: 2 mA 
Max. Load: 5 kΩ 
Current mode 
Range: 0–20 mA (Pr.03-31 = 1) / 4–20 mA (Pr.03-31 = 2) 
corresponds to the maximum operating range of the 
control target, maximum load 500 Ω 
AFM resolution=10 bits