Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-01-5 
 
 When Fcmd > Fmin and Fcmd < Fstart: 
If Flow < Fcmd, the drive runs directly by Fcmd. 
If Flow ≥ Fcmd, the drive runs with Fcmd, and then rises to Flow according to acceleration time. 
  The drive’s output frequency goes directly to 0 when decelerating to Fmin. 
 
01-10 
Output Frequency Upper Limit 
 
 
   
 Default: 599.00 
 
 
Settings 0.00–599.00 Hz 
 
01-11 
Output Frequency Lower Limit 
 
 
   
 Default: 0.00 
 
 
Settings 0.00–599.00 Hz 
 If the output frequency setting is higher than the upper limit (Pr.01-10), the drive runs with the 
upper limit frequency. If the output frequency setting is lower than the lower limit (Pr.01-11) but 
higher than the minimum output frequency (Pr.01-07), the drive runs with the lower limit frequency. 
Set the upper limit frequency > the lower limit frequency (Pr.01-10 setting value must be > Pr.01-
11 setting value). 
 If the slip compensation function (Pr.07-27) is enabled for the drive, the drive’s output frequency 
may exceed the Frequency command.