Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-02-24
 
02-19 
Terminal Counting Value Reached (Returns to 0) 
 
 
   
 Default: 0 
 
 
Settings 0–65500 
 You can set the input point for the counter using the multi-function terminal MI6 as a trigger 
terminal (set Pr.02-06 to 23). When counting is completed, the specified multi-function output 
terminal is activated (Pr.02-13, Pr.02-14, Pr.02-36, Pr.02-37 are set to 18). Pr.02-19 cannot be 
set to 0 at this time. 
Example: When the displayed value is c5555, the drive count is 5,555 times. If the displayed 
value is c5555, the actual count value is 55,550–55,559. 
 
02-20 
Preliminary Counting Value Reached (Does Not Return to 0) 
 
 
   
 Default: 0 
 
 
Settings 0–65500 
 When the counter value counts from 1 to reach this value, the corresponding multi-function 
output terminal is activated (Pr.02-13, Pr.02-14, Pr.02-36, Pr.02-37 are set to 17). You can use 
this parameter as the end of counting to make the drive run from the low speed to stop. 
 
 
02-21 
Digital Output Gain (DFM) 
 
 
   
 Default: 1 
 
 
Settings 1–166 
 Sets the signal for the digital output terminals (DFM-DCM) and the digital frequency output 
(pulse, work period=50%). The output pulse per second = output frequency × Pr.02-21. 
 
02-22 
Desired Frequency Reached 1 
 
 
   
  Default: 60.00 / 50.00 
 
 
Settings 0.00–599.00 Hz 
 
02-23 
The Width of the Desired Frequency Reached 1 
 
 
   
 Default: 2 
 
 
Settings 0.00–599.00 Hz 
 
02-24 
Desired Frequency Reached 2 
 
 
   
  Default: 60.00 / 50.00 
 
 
Settings 0.00–599.00 Hz 
 
02-25 
The Width of the Desired Frequency Reached 2 
 
 
   
 Default: 2.00 
 
 
Settings 0.00–599.00 Hz