Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-11-54 
Diagram 24 
CiA402 object 
0x6098H 
Z  Y  X 
Function Description 
Homing 
Method 
Home 
Limit 
Z-phase 
Signal 
Setting 
Homing 
Mode 
26 1 2 6 
Execute homing position control in the forward direction 
and use the ORG switch (from 1 to 0) as the origin. When 
encountering the positive limit switch, the direction is 
reversed to locate the origin. 
1.  The initial movement is in the forward direction. 
2.  When moving in the forward direction and encountering the positive limit switch, the movement 
direction is reversed and waits for the falling-edge trigger of the positive limit switch. 
3.  When moving in the reverse direction and encountering the rising edge of the ORG switch, the 
movement direction is reversed. 
4.  Then, wait for the falling-edge trigger of the ORG switch as the origin. 
   
A homing failure occurs when the following condition happen: 
1.  If a negative limit switch signal is encountered when the motor moves in the reverse direction, a 
homing failure occurs. 
2.  If no positive limit switch signal is encountered in the homing process mentioned above, and time-
out is triggered, then a homing failure occurs. 
 
NL PL
1
ORG
5
2
3
4
7
Collision
Limit 
switch
6