Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-11-64 
 
11-78 
HALT Revived Selection 
 
 
   
 Default: 0 
 
 
Settings 0: Stopped 
1: Continue according to the previous position command 
 When executing multi-step positioning position control through communications: If 6000h bit3 = 1, 
the drive stops at zero speed in a Servo ON status according to the deceleration time for position 
control. If 6000h bit3 = 0, the drive acts according to Pr.11-78 settings: 
When Pr.11-78 = 0, the drive is in complete stop, and Servo ON remains. 
When Pr.11-78 = 1, the drive resumes with previous position command. 
Control Source 
Position 
bit  Value  bit name  Profile Position Control Mode (pp)   
6000h 3 
0 
HALT 
Acts according to Pr.11-78 settings 
1 
Stops according to the deceleration 
time for position control