Chapter 14 Fault Codes and DescriptionsC2000 Plus 
 
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
84 
 
Output phase loss 
W phase (OPHL) 
W phase output phase loss 
Action and Reset 
Action condition  Pr.06-47 
Action time 
Pr.06-46 
Pr.06-48: Use the setting value of Pr.06-48 first. If DC braking func
use that of Pr.06-46. 
Fault treatment parameter 
Pr06-45 
0: Warn and keep operation 
1: Fault and ramp to stop 
2: Fault and coast to stop 
3: No warning 
Reset method  Manual reset 
Reset condition  Reset immediately 
Record  When Pr.06-45 = 1 or 2, OPHL is a “Fault”, and the fault is recorded. 
Cause  Corrective Actions 
Unbalanced three-phase 
impedance of the motor 
Replace the motor. 
Check if the wiring is incorrect  Check the cable and replace it if necessary. 
Check if the motor is a single-
phase motor 
Choose a three-phase motor. 
Check if the current sensor is 
broken 
Check if the control board cable is loose. If yes, reconnect the cable and run the
drive to test. If the fault still occurs, return to the factory for repair. 
Check if the three-
phase current is balanced with a current clamp meter. If the 
current is balanced and the OPHL fault still occurs
, return to the factory for repair.   
Check if the drive capacity is 
larger than the motor capacity 
Choose the drive that matches the motor capacity