Chapter 12 Descriptions of Parameter SettingsMS300 
352 
 
 Set up Pr.01-54 and Pr.05-66 before setting up Pr.05-67 to ensure that the motor operates 
normally. 
No-load Current for Induction Motor 3 (A) 
Default: Depending on the 
model power 
 The default is 40% of the motor’s rated current. 
Stator Resistance (Rs) for Induction Motor 3 
Default: Depending on the 
model power 
Full-load Current for Induction Motor 4 (A) 
Default: Depending on the 
model power 
10–120% of the drive’s rated current 
 Set this value according to the rated current of the motor as indicated on the motor nameplate. 
The default is 90% of the drive’s rated current.   
Example: The rated current for a 7.5 HP (5.5 kW) motor is 25 A. The default is 22.5 A.   
The setting range is 2.5–30 A (25 × 10% = 2.5 A and 25 × 120% = 30 A).
Rated Power for Induction Motor 4 (kW) 
Default: Depending on the 
model power 
 Sets the rated power for motor 4. The default is the drive’s power value.
Rated Speed for Induction Motor 4 (rpm) 
Default: Depending on the 
motor’s number of poles 
0–xxxxx rpm (Depending on the motor’s number of poles) 
1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles) 
 Sets the rated speed for the motor as indicated on the motor nameplate. 
Number of Poles for Induction Motor 4 
 Sets the number of poles for the motor (must be an even number). 
 Set up Pr.01-63 and Pr.05-72 before setting up Pr.05-73 to make sure the motor operates 
normally.