Chapter 12 Description of Parameter SettingsMS300 
 
466 
 
               
 
 Basic motor parameters adjustment 
1.  Parameter reset: 
Reset Pr.00-02 = 9 (50 Hz) or 10 (60 Hz) to the default value. 
2.  Select PM motor type: 
Pr.05-33 = 0 (IM) 
3.  Motor nameplate parameter setting: 
Motor 1 rated / base frequency (Hz) 
Motor 1 rated / base voltage (V
AC
) 
Full-load current for induction motor 1 (A) 
Rated power for induction motor 1 (kW) 
Rated speed for induction motor 1 (rpm) 
Number of poles for induction motor 1 (poles) 
4.  Motor auto-tuning: 
Press RUN to start auto-tuning of IM magnetic flux curve dynamic test for Pr.05-00 = 1 or 6 
(motor is running). Make sure the motor executes auto-tuning under break-away load 
condition. Check if there are motor parameters after auto-tuning. 
Stator resistance (Rs) for induction motor 1 (Ω) 
Rotor resistance (Rr) for induction motor 1 (Ω) 
Magnetizing inductance (Lm) for induction motor 1 (mH) 
Stator inductance (Lx) for induction motor 1 (mH)