EasyManuals Logo

Delta VFD17AMS43AFSAA User Manual

Delta VFD17AMS43AFSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #511 background imageLoading...
Page #511 background image
Chapter 13 Warning CodesMS300
502
ID No.
Display on LCD Keypad
Warning Name
Description
41
CANopen station
address error (CAdn)
CANopen station address error (only supports 1–127)
Action and Reset
Action Condition
CANopen station address error
Action Time
Immediately act when the fault is detected
Warning Setting Parameter
N/A
Reset Method
Manual Reset
Reset Condition
Pr.00-02 = 7
Record
When Pr.00-21 ≠ 3, CAdn is a “Warning”, and the warning is not recorded.
Cause
Corrective Actions
Incorrect setting of CANopen
station address
1. Disable CANopen (Pr.09-36 = 0)
2. Reset CANopen (Pr.00-02 = 7)
3. Reset CANopen station address (Pr.09-36)

Table of Contents

Other manuals for Delta VFD17AMS43AFSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD17AMS43AFSAA and is the answer not in the manual?

Delta VFD17AMS43AFSAA Specifications

General IconGeneral
BrandDelta
ModelVFD17AMS43AFSAA
CategoryDC Drives
LanguageEnglish

Related product manuals