Chapter 14 Fault CodesMS300 
593 
 
Data is written to read-
only address (CE4) 
Data is written to read-only address 
When the data is written to read-only address. 
Fault Treatment Parameter 
Incorrect communication 
command from the upper unit 
Check if the communication command is correct. 
Malfunction caused by 
interference 
Verify the wiring and grounding of the communication circuit. It is recommended 
to separate the communication circuit from the main circuit, or wire in 90 degree 
for effective anti-interference performance. 
Different communication setting 
from the upper unit 
Check if the setting for Pr.09-04 is the same as the setting for the upper unit. 
Disconnection or bad connection 
of the cable 
Check the cable and replace it if necessary.