Chapter 12 Description of Parameter SettingsCP2000   
 
12.1-02-21 
 Example:  
When Pr.02-53 displays 0003h (hex), it means that RY1 and RY2 are used by PLC. 
 
 
 
Display the Frequency Command Executed by External Terminal 
  
 
  Default: Read only   
  Settings  0.00–599.00 Hz (Read only) 
  When  you  set  the  source  of  the  frequency command  as  the  external  terminal,  if  Lv  or  Fault 
occurs, the external terminal frequency command is saved in this parameter.   
 
 
IO Card Types 
  
 
  Default: Read only 
  Settings  1: EMC-BPS01   
    4: EMC-D611A 
    5: EMC-D42A 
    6: EMC-R6AA   
    11: EMC-A22A 
 
 
Preheating Output Current Level 
  
 
  Default: 0   
  Settings  0–100% 
  When a motor drive is not in operation (STOP) and is placed in a cold and humid environment, 
enabling the preheating function to output DC current to heat up the motor drive can prevent the 
invasion of humidity into the motor drive, which creates condensation affects the normal function 
of the motor drive. 
  Sets the output current level from the motor drive to the motor after enabling the preheating. The 
percentage of the preheating DC current is 100% of the rated current of the motor drive (Pr.05-01, 
Pr.05-13 and Pr.05-34). When setting this parameter, slowly increase the percentage to reach 
the sufficient preheating temperature. 
 
 
Preheating Output Cycle 
  
 
  Default: 0   
  Settings  0–100% 
  Sets the output current cycle of preheating. 0–100% corresponds to 0–10 seconds. When set to 
0%, there is no output current. When set to 100%, there is a continuous output. For example, 
when set to 50%, a cycle of preheating goes from OFF (5 seconds) to ON (5 seconds), and vice 
versa.