Chapter 12 Descriptions of Parameter SettingsMS300 
312 
 
Status of the Safety Output 
Analog input level 
reached 
The multi-function output terminals operate when the analog 
input level is between the high level and the low level. 
Pr.03-44: Select one of the analog input channels (AVI, ACI) to 
be compared. 
Pr.03-45: The high level for the analog input, default is 50%. 
Pr.03-46: The low level for the analog input, default is 10%. 
If analog input > Pr.03-45, the multi-function output terminal 
operates. If analog input < Pr.03-46, the multi-function output 
terminal stops output. 
Activates when over-torque is detected. Pr.14-75 sets the over- 
torque detection level. Pr.14-76 sets the over-torque detection 
time (refer to Pr.14-74–14-76). 
Activates when over-torque is detected. Pr.14-78 sets the over- 
torque detection level. Pr.14-79 sets the over-torque detection 
time (refer to Pr.14-77–14-79). 
When the drive runs FWD, the output terminal for forward 
running is closed; when the drive stops, the output terminal for 
forward running is open. 
When the drive runs REV, the output terminal for reverse running 
is closed; when the drive stops, the output terminal for reverse 
running is open. 
Multi-Function Output Direction 
0000h–FFFFh (0:N.O.; 1:N.C.) 
 This parameter is in hexadecimal. 
 This parameter is set by a bit. If the bit is 1, the corresponding multi-function output acts in an 
opposite way. 
Example: Assume Pr.02-13 = 1 (indication when the drive is operating). If the output is positive, 
and the bit is set to 0, then Relay is ON when the drive runs and is OFF when the drive stops. 
On the contrary, if the output is negative, and the bit is set to 1, then the Relay is OFF when the 
drive runs and is ON when the drive stops.