EasyManuals Logo

Delta VFD4A8MS23ANSAA User Manual

Delta VFD4A8MS23ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #412 background imageLoading...
Page #412 background image
Chapter 12 Descriptions of Parameter SettingsMS300
403
Parallel connection
08-08
Feedback Signal Detection Time
Default: 0.0
Settings
0.03600.0 sec.
Valid only when the feedback signal is ACI (420 mA).
This parameter sets the detection time for abnormal PID signal feedback. You can also use it
when the system feedback signal response is extremely slow. (Setting the detection time to 0.0
disables the detection function.)
08-09
Feedback Signal Fault Treatment
Default: 0
Settings
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: Warn and operate at last frequency
Valid only when the feedback signal is ACI (420 mA).
Sets the treatments when the PID feedback signal is abnormal.
08-10
Sleep Level
Default: 0.00
Settings
0.00–599.00 Hz / 0.00200.00%
08-11
Wake-up Level
Default: 0.00
Settings
0.00–599.00 Hz / 0.00200.00%
Determines the sleep frequency, and if the sleep time and the wake-up frequency are enabled or
disabled.
Pr.08-10 = 0: Disabled; Pr.08-10 0: Enabled

Table of Contents

Other manuals for Delta VFD4A8MS23ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD4A8MS23ANSAA and is the answer not in the manual?

Delta VFD4A8MS23ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD4A8MS23ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals