Chapter 12 Description of Parameter SettingsCP2000   
 
 
12.1-02-18 
 
 
Output Current Level Setting for Multi-function Output Terminals 
  
 
  Default: 0 
  Settings  0–150% 
 When  the  drive  outputs  current  higher  than  or  equal  to  Pr.02-33,  the  multi-function  output 
parameters active (Pr.02-13, Pr.02-14, and Pr.02-15 are set to 27). 
   When the drive outputs current lower than Pr.02-33, the multi-function output parameters active 
(Pr.02-13, Pr.02-14, and Pr.02-15 are set to 28). 
 
 
Output Frequency Setting for Multi-function Output Terminals 
 
 
  Default: 3.00 
  Settings  0.00–599.00 Hz 
 When the drive outputs frequency higher than or equal to Pr.02-34 (actual output frequency H ≥ 
Pr.02-34), the multi-function terminal active (Pr.02-13, Pr.02-14 and Pr.02-15 are set to 29). 
 When the drive outputs frequency lower than Pr.02-34 (actual output frequency H < Pr.02-34), the 
multi-function terminals active (Pr.02-13, Pr.02-14 and Pr.02-15 are set to 30). 
 
 
External Operation Control Selection after Reset and Activate 
 
 
  Default: 0 
  Settings  0: Disable 
    1: Drive runs if the RUN command remains after reset or re-boot 
 Setting  1:  the  driver  automatically  executes  the  RUN  command  under  the  following 
circumstances, pay extra attention on this. 
  Status 1: After the drive is powered on and the external terminal for RUN stays ON, the drive 
runs. 
  Status 2: After clearing a fault once a fault is detected and the external terminal for RUN 
stays ON, you can run the drive by pressing RESET key. 
 
 
Display the Status of Multi-function Input Terminal 
 
    
  Default: Read only 
   Settings  Monitoring status of multi-function input terminal