Chapter 13 Warning CodesCP2000
13-34
ID No. Display on LCD Keypad Warning Name Description
77
ExCom IO Net break
(ECio)
IO connection break off
Action and Reset
Action level IO connection between the communication card and the master is broken off
Action time Immediately acts
Warning setting parameter N/A
Reset method Manual reset
Reset condition Immediately reset
Record N/A
Cause Corrective Actions
The cable is loose Re-install the cable
Incorrect parameter setting for
master communication
Check the setting for master communication parameter
ID No. Display on LCD Keypad Warning Name Description
78
ExCom Parameter
data error
(ECPP)
Profibus parameter data error
Action and Reset
Action level N/A
Action time N/A
Warning setting parameter N/A
Reset method Manual reset
Reset condition Immediately reset
Record N/A
Cause Corrective Actions
The GSD file is incorrect Get the correct GSD file from the software
ID No. Display on LCD Keypad Warning Name Description
79
ExCom configuration
data error
(ECPi)
Profibus configuration data error
Action and Reset
Action level N/A
Action time N/A
Warning setting parameter N/A
Reset method Manual reset
Reset condition Immediately reset
Record N/A
Cause Corrective Actions
The GSD file is incorrect Get the correct GSD file from the software