b) Perform the setup steps onscreen. You must allow ELOG to install the driver for the
ELITEpro XC to work correctly.
c) If the driver installation fails, see the Troubleshooting Driver Installation section of the
ELOG 14 Operator’s Guide.
3) Set the computer aside and proceed with the next section.
Set Up the ELITEpro XC
1) Connect the Current Transformers (CTs) to the wires of the load you are measuring. Orient
the CT so that the arrow on the CT case points towards the load.
NOTE: Use only inherently safe 333mV output CTs supplied by DENT. Never use current output CTs.
The UL listing covers the use of the following DENT Instruments CTs that are UL Recognized and
have been evaluated to IEC 61010-1:
CT-HSC-020-X (20A Mini), CT-HSC-050-X (50A Mini), CT-HMC-0100-X (100A Midi), and the CT-HMC-
0200-X (200A Midi). The use of any other CT will invalidate the UL Listing of the ELITEpro XC.
2) Make your voltage connections (L1, L2, and N). In this scenario, L3 is not used and may be set
aside.
3) Connect the Current Transformers to the ELITEpro XC.
Connect the CTs to the black (Phoenix-style) connectors on the ELITEpro XC’s end panel. Start with
the left-most pair of connections which is Channel One.
The high (+) wire of the CT (the white, banded, or numbered wire depending on CT type)
should go to the left (+) screw terminal of each channel input.
The low (-) CT wire (the black or unbanded wire) should go into the right (-) screw
terminal of the channel input.
If you are using RōCoil CTs, be sure to connect the bare wire to the “S” (shield) screw
terminal. This reduces interference and improves the accuracy of the CT.