20
ELECTROVAP KIT MC
Installation - Step 3
ALL WORKS CONCERNED WITH ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY A SKILLED AND QUALIFIED PERSONNEL
KIT MC steam humidifier in 3 X 460V - 50/60 Hz
KIT MC
Production
(KG/St)
In Imaxi Pmaxi
Cylinder size
Steam Torroidal
( A ) ( A ) ( KW )
diameter transformer
5
5 4.8 5.4 4,25 Small 25 Loop
8
8 7.6 8.4 6,61 Small 25 Straight through
10
10 9.6 10.6 8,26 Small 25 Straight through
15-2
15 14.3 15.5 12,19 Small 25 Straight through
20
20 19.1 20.5 16,13 40 large 40 Straight through
30
30 28.7 30.6 24,07 40 large 40 Split
40
40 40.7 38.2 32.01 2 x 40 large 40 Straight through
50
50 47.8 50.7 39,88 2 x 40 large 40 Split
60
60 57.4 60.8 47,83 2 x 40 large 40 Split
KIT MC steam humidifier in 3 X 480V - 50/60 Hz
KIT MC
Production
(KG/St)
In Imaxi Pmaxi
Cylinder size
Steam Torroidal
( A ) ( A ) ( KW )
diameter transformer
5
5 4.6 5.2 4,25 Small 25 Loop
8
8 7.3 8.0 6,58 Small 25 Straight through
10
10 9.2 10.1 8,27 Small 25 Straight through
15-2
15 13.7 14.9 12,22 Small 25 Straight through
20
20 18.3 19.6 16,09 40 large 40 Straight through
30
30 27.5 29.3 24,06 40 large 40 Split
40
40 39.6 38.9 31,95 2 x 40 large 40 Straight through
50
50 45.8 48.5 39,85 2 x 40 large 40 Split
60
60 55 57.7 47,37 2 x 40 large 40 Split