DEVIreg™ Smart
9Installation Guide
Note: A floor sensor is recommended in all floor
heating applications and mandatory to thin mats
and under wooden floors to reduce the risk of over-
heating the floor.
Place the floor sensor in a protecting plastic conduit
in the floor construction in an appropriate place,
where the floor is not exposed to sunlight or draft
from door openings.
Equally distant and >2 cm from the heating cables
on both sides.
The conduit should
be flush with the floor
surface, countersink
the conduit if neces-
sary and possible.
Route the conduit to
the connection box.
The bending radius of the conduit must be min 50
mm.